LC1D32P7 TeSys KONTAKTOR 32A, 230V SCHNEIDER
range |
TeSys
|
|
---|---|---|
product name |
TeSys D
|
|
product or component type |
Contactor
|
|
device short name |
LC1D
|
|
contactor application |
Resistive load
Motor control |
|
utilisation category |
AC-1
AC-3 AC-4 |
|
poles description |
3P
|
|
power pole contact composition |
3 NO
|
|
[Ue] rated operational voltage |
Power circuit <= 690 V AC 25…400 Hz
Power circuit <= 300 V DC |
|
[Ie] rated operational current |
32 A 60 °C) <= 440 V AC AC-3 power circuit
50 A 60 °C) <= 440 V AC AC-1 power circuit |
|
motor power kW |
7,5 kW 220…230 V AC 50/60 Hz AC-3)
15 kW 380…400 V AC 50/60 Hz AC-3) 15 kW 415…440 V AC 50/60 Hz AC-3) 18,5 kW 500 V AC 50/60 Hz AC-3) 18,5 kW 660…690 V AC 50/60 Hz AC-3) 7,5 kW 400 V AC 50/60 Hz AC-4) |
|
motor power HP (UL / CSA) |
5 hp 230/240 V AC 50/60 Hz 1 phase
10 hp 230/240 V AC 50/60 Hz 3 phases 30 hp 575/600 V AC 50/60 Hz 3 phases 2 hp 115 V AC 50/60 Hz 1 phase 7,5 hp 200/208 V AC 50/60 Hz 3 phases 20 hp 460/480 V AC 50/60 Hz 3 phases |
|
control circuit type |
AC 50/60 Hz
|
|
[Uc] control circuit voltage |
230 V AC 50/60 Hz
|
|
auxiliary contact composition |
1 NO + 1 NC
|
|
[Uimp] rated impulse withstand voltage |
6 kV IEC 60947
|
|
overvoltage category |
III
|
|
[Ith] conventional free air thermal current |
10 A 60 °C signalling circuit
50 A 60 °C power circuit |
|
Irms rated making capacity |
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1 550 A 440 V power circuit IEC 60947 |
|
rated breaking capacity |
550 A 440 V power circuit IEC 60947
|
|
[Icw] rated short-time withstand current |
60 A 40 °C – 10 min power circuit
138 A 40 °C – 1 min power circuit 260 A 40 °C – 10 s power circuit 430 A 40 °C – 1 s power circuit 100 A – 1 s signalling circuit 120 A – 500 ms signalling circuit 140 A – 100 ms signalling circuit |
|
associated fuse rating |
10 A gG signalling circuit IEC 60947-5-1
63 A gG <= 690 V type 1 power circuit 63 A gG <= 690 V type 2 power circuit |
|
average impedance |
2 mOhm – Ith 50 A 50 Hz power circuit
|
|
[Ui] rated insulation voltage |
Power circuit 600 V CSA
Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL Power circuit 690 V IEC 60947-4-1 |
|
electrical durability |
1,65 Mcycles 32 A AC-3 <= 440 V
1,4 Mcycles 50 A AC-1 <= 440 V |
|
power dissipation per pole |
2 W AC-3
5 W AC-1 |
|
Front cover |
With
|
|
mounting support |
Rail
Plate |
|
standards |
CSA C22.2 No 14
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
|
product certifications |
UL
GOST CSA BV LROS (Lloyds register of shipping) RINA GL CCC DNV |
|
connections – terminals |
Control circuit screw clamp terminals 2 1…2,5 mm²flexible with cable end
Control circuit screw clamp terminals 1 1…4 mm²flexible without cable end Control circuit screw clamp terminals 2 1…4 mm²flexible without cable end Control circuit screw clamp terminals 1 1…4 mm²flexible with cable end Control circuit screw clamp terminals 1 1…4 mm²solid without cable end Control circuit screw clamp terminals 2 1…4 mm²solid without cable end Power circuit screw clamp terminals 1 2,5…10 mm²flexible without cable end Power circuit screw clamp terminals 2 2,5…10 mm²flexible without cable end Power circuit screw clamp terminals 1 1…10 mm²flexible with cable end Power circuit screw clamp terminals 2 1,5…6 mm²flexible with cable end Power circuit screw clamp terminals 1 1,5…10 mm²solid without cable end Power circuit screw clamp terminals 2 2,5…10 mm²solid without cable end |
|
tightening torque |
Control circuit 1,7 N.m screw clamp terminals flat Ø 6 mm
Control circuit 1,7 N.m screw clamp terminals Philips No 2 Power circuit 2,5 N.m screw clamp terminals flat Ø 6 mm Power circuit 2,5 N.m screw clamp terminals Philips No 2 |
|
operating time |
4…19 ms opening
12…22 ms closing |
|
safety reliability level |
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
|
mechanical durability |
15 Mcycles
|
|
maximum operating rate |
3600 cyc/h 60 °C
|
coil technology |
Without built-in suppressor module
|
|
---|---|---|
control circuit voltage limits |
0.3…0.6 Uc −40…70 °C drop-out AC 50/60 Hz
0.8…1.1 Uc −40…60 °C operational AC 50 Hz 0.85…1.1 Uc −40…60 °C operational AC 60 Hz 1…1.1 Uc 60…70 °C operational AC 50/60 Hz |
|
inrush power in VA |
70 VA 60 Hz 0,75 20 °C)
70 VA 50 Hz 0,75 20 °C) |
|
hold-in power consumption in VA |
7,5 VA 60 Hz 0,3 20 °C)
7 VA 50 Hz 0,3 20 °C) |
|
heat dissipation |
2…3 W 50/60 Hz
|
|
auxiliary contacts type |
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1 |
|
signalling circuit frequency |
25…400 Hz
|
|
minimum switching current |
5 mA signalling circuit
|
|
minimum switching voltage |
17 V signalling circuit
|
|
non-overlap time |
1,5 ms on de-energisation between NC and NO contact
1,5 ms on energisation between NC and NO contact |
|
insulation resistance |
> 10 MOhm signalling circuit
|
|
contact compatibility |
M2
|
|
compatibility code |
LC1D
|
|
motor power range |
7…11 kW 200…240 V 3 phases
15…25 kW 380…440 V 3 phases 15…25 kW 480…500 V 3 phases |
|
motor starter type |
Direct on-line contactor
|
|
contactor coil voltage |
230 V AC standard
|